Special Features
Bpanelboard arranged in horizontal configuration w/enclosure back as bottom side and include hinged cover on topside, weatherproofed, circuit breakers to be 3-pole w/interrupting ratingsat 480v ac in accordance w/fed-spec w-c-375a amend 4, be classes and trip ratings connected to 3-phase, 1200ampere bus bar, cl 2f 100 amp trip-2 ea, cl 3b 225 amp trip-6 ea, cl 4b 400 amp non-automatic trip-4 ea, conduit bushings to be two-piece insulating conforming to type 3, cl 1, kind r, fed-spec w-c-408b in sizes and quantities, 2 in-2 ea f/10 amp circuit breaker conductor, 3 in-6 ea f/225 amp circuit breaker conductor, 4 in-4 ea f/400 amp circuitbreaker conductor, conduit bushings installed in enclosure bottom side in relative location to circuit breakers they are to be utilized, 1 ground terminal w/solderless lug, solderless lug shall be compatible w/aluminum and copper and have the capacity f/1 no. 6-awg copper conductor, conforms to porta-power pac inc, dwg no. 105100 or equal
Description
84.000 inches maximum overall length.
Overall Height
36.000 inches
Overall Width
36.000 inches
Mounting Method
Floor
Panel Material
Aluminum
Input Phase
Three
Inclosure Feature
Waterproof
Output Frequency Rating
60 hertz
Panel Quantity
1
Electrical Input Quantity
1
Input Voltage Rating
120.0 ac pounds per hour dry and 480.0 ac pounds per hour with retaining chain